Extinguishant Control Panel MN: HP102-4
General Description:
The automatic extinguisher control panel is designed in accordance with European standards EN54-2 and EN54-4 Fire Detection and Fire Alarm systems Control and Indicating Equipment and EN12094-1 Fixed firefighting systems – Components for gas extinguishing systems – Part 1: Requirements and test methods for electrical automatic control and delay devices.
The control equipment is a combined fire alarm control panel and extinguishing system and has four detection zones, any or all of which are capable of contributing to the extinguishant release decision. Control panels have an integral, mains powered battery charger and power supply designed in accordance with the requirements of EN54-4.
Features:
Class B Initiating Device Circuits (IDCs)
4 zones accept conventional detectors and any normally open contact device
2 Class B Notification Appliance Circuits (NACs) One Form-A Alarm Relay
One Form-A Trouble Relay Two Form-A Stage Relay
3.0 amps of system power
Max 30 conventional detectors in one zone. Each Zone can be disabled
Sound output can be disabled Manual active sound output enabled
Can connect max 32 repeater panels by RS485 communication port
Description
Specifications
Primary AC | 90-270VAC 50/60 Hz |
Power supply rating | 3 Amps @ 24VDC |
ALARM&FAULT Relay rating | 2A & 30VAC, resistive |
Normal Initiating Operating
Voltage |
23VDC, Maximum 26VDC, regulated |
Minimum Battery Size 2 x 12V Required (Ah) | 7 |
Number of Sense Zones | 4 |
Maximum Number of Detectors | 30 |
Firing Resistance (Ohms) | 510 ± 200 |
Sense Zone End of Line (Ohms) | 4k7 |
Sounder Voltage (V DC) | 27 |
Number of Sound Zones (NACs) | 2 |
Maximum Sound Current per Zone | 500mA |
Max. Sounder Number of per Zone | 5 |
Alarm Zone End of Line (Ohms) | 10k |
Max. Auxiliary Supply Current(mA) | 500mA |
Extinguishant release output | 2 Amp@28VDC |
Extinguishant release delay time | Adjustable 0 to 75 seconds |
Extinguishant output end of line | 10K±5% 1/2 Watt resistor |
SIL, AL, FLT, RST inputs | Switched – max 1k ohms |
Terminal capacity | 0.5mm2 to 2.5mm2 wires |
Extract contact rating | 2A /30VDC maximum for each |
Operating Humidity Range | 10% to 93% Relative Humidity, Non-condensing |
Operating Voltage Range | -10°C to 50°C |
Panel Dimensions (mm) | 383*295*87(L*W*D) |
Panel Weight [Without Batteries] | 5kg |