Conventional Fire Alarm Control Panel Model Number: HP1010-02/-04/-08/-16

General Description:

The HP1010 Series conventional fire alarm control panel is a 24 volt, 2 to 16 zones,

class B, conventional Fire Alarm Control Panel. Designed exclusively to meet the latest market requirements and future ULC codes, the highly cost-effective Series can be used in a

variety of low- to mid-sized applications. The panel uses conventional input devices.

The panel accepts water flow devices, two-wire smoken or heat detectors, four-wire smoken or heat detectors,call points and other normally-open contact devices.

Outputs include four Notification Appliance Circuits (NAC, SOUND1-4), three standard Form-A relays (alarm, trouble and supervisory) and an EIA-485 port to interface with repeaters.

The panel is field programmable via the panel keypad. It also supervises all wiring, AC voltage and battery level.

Features:

2,4,8,16 Class B Initiating Device Circuits (IDCs) All zones accept conventional detectors and any normally open contact device

1-4 Class B Notification Appliance Circuits (NACs) One Form-A Alarm Relay

One Form-A Trouble Relay One Form-A Supervisory Relay

3.0 amps of system power

Max 30 conventional detectors in one zone. Auto/Manual mode setting enable walk test. Each Zone can be disabled

Sound output can be disabled. Manual active sound output enabled. Manual active sound output enabled.

Able to report short and broken circuit of detection zones. Designed with standby batteries and space provision for two sealed lead-acid batteries.

Testing and disable functions.

Can connect maximum 32 repeater panels by RS485 communication port.

Share with friends

Description

Specifications

Primary AC 90-270VAC 50/60 Hz
Power supply rating 3 Amps @ 24VDC
ALARM&FAULT Relay rating 2A & 30VAC, resistive
Normal Initiating Operating

Voltage

23VDC, Maximum 26VDC, regulated
Minimum Battery Size 2 x 12V Required (Ah) 10Ah for 4 to 16 zones 4.5Ah for 2 zones
Number of Sense Zones 1 to16
Maximum Number of Detectors 30
Firing Resistance (Ohms) 510 ± 200
Sense Zone End of Line (Ohms) 4k7
Sounder Voltage (V DC) 27
Number of Sound Zones (NACs) 1 to 4
Maximum Sound Current per Zone 500mA
Max. Sounder Number of per Zone 5
Alarm Zone End of Line (Ohms) 10k
Max. Auxiliary Supply Current(mA) 500mA
Panel Dimensions (mm)(L*W*D) 4 to 16 Zones: 370*440*100

2 Zones: 205*258*81

Panel Weight [Without Batteries] 4 to16 Zones: 6.6kg 2 Zones: 2.2kg