Addressable Fire Alarm Control Panel Model HP 201
General Description:
HP201 is an addressable fire alarm control panel capable to connect up to 250 HST addressable devices per loop. With its extra large graphical display, it configures almost all panel settings via its very simple interface or with it’s built in PC interface via
HST RINGER configuration software. It stores almost all different actions monitored up to 4000 event log records.
HP201 covers all small to medium size fire detection system needs
Description
Specifications
Primary AC | 90-270VAC 50/60 Hz |
Main supply output voltage(VDC) | 27VDC |
Main supply output current(mA) | 6.5A max. |
Panel main fuse | 5A |
Minimum Battery Size 2 x 12V Required (Ah) | 7 |
Battery charging voltage(VDC) | 27VDC |
Battery charging current(mA) | 700 |
Programmable volatge output | 1Amp@24VDC |
Free volatge output | 1Amp@24VDC |
Sounder lines | 1Amp@24VDC ressetable fuse |
Sounder Zone End of Line (Ohms) | 10k |
Detection loop current(mA) | 190mA max |
Display | Graphical LCD 240X128 |
Current consumption (normal)(mA) | 410 max.(500 Devices on line) |
Current consumption (alarm)(mA) | 1670 max.(500 Devices on line) |
Relay contacts capacity | 2 Amp@28VDC |
Protocol | HST CLIP |
Computer interface | RS485&RS232 |
3 Dry inputs | Switched – max 1k ohms |
Terminal capacity | 0.5mm2 to 2.5mm2 wires |
Extract contact rating | 2A /30VDC maximum for each |
Operating Humidity Range | 10% to 93% Relative Humidity, Non-condensing |
Operating Voltage Range | -10°C to 50°C |
Panel Dimensions (mm) | 450*370*120(L*W*D) |
Panel Weight (Without Batteries) | 6kg |