100 Series Conventional Detector model number HD101B/HD102B/HD103B
General Description:
This series detector can be used in all areas where
photoelectric smoke detector,heat detector or multi
detector is required. It is suited for fires ranging from
smoldering to flaming fires.
This series detectro is designed to provide open area
protection and to be used with most conventional fire
alarm control panel.
Two LEDs on each detector provide local 360° visible for
indication of status. In the normal condition the LEDs
flash red every 5 seconds. When the detector senses
smoke or heat goes into pre-alarm sensitivity the LEDs
will flash red every 1 second. When the detector senses
smoke or heat goes into alarm the LEDs will latch on red.
The alarm can be reset only by a momentary power
interruption.
The detectors meets the requirements of the EN54-5&7
standards and were got the certification by Intertek
Description
HD101B Coventional Smoke Detector
Operating Voltage
Range
16 to 28VDC Volts Non-polarized
Standby Current
≤40µA @ 24 VDC
Maximum Alarm
Current (LED on)
≤30mA @ 24 VDC
Operating Humidity
Range
10% to 93% Relative Humidity,
Non-condensing
Operating Voltage
Range
-10°C to 50°C
Smoke Sensitivity
0.12 to 0.25dB/m
Height
55 mm (Installed in Base)
Diameter
103 mm
Weight
155 g
HD102B Coventional Heat Detector
Operating Voltage
Range
16 to 28VDC Volts Non-polarized
Standby Current
≤40µA @ 24 VDC
Maximum Alarm
Current (LED on)
≤30mA @ 24 VDC
Operating Humidity
Range
10% to 93% Relative Humidity,
Non-condensing
Operating Voltage
Range
-10°C to 50°C
Temperature Class
A2R
Height
55 mm (Installed in Base)
Diameter
103 mm
Weight
155 g
HD103B Coventional Multi Detector
Operating Voltage
Range
16 to 28VDC Volts Non-polarized
Standby Current
≤40µA @ 24 VDC
Maximum Alarm
Current (LED on)
≤30mA @ 24 VDC
Operating Humidity
Range
10% to 93% Relative Humidity,
Non-condensing
Operating Voltage
Range
-10°C to 50°C
Sensitivity(Smoke&Heat) 0.12 to 0.25dB/m & A2R
Height
55 mm (Installed in Base)
Diameter
103 mm
Weight
155 g